7 cableado del circuito principal – Yaskawa CIMR-LE Manual del usuario

Página 71

Advertising
background image

3.7 Cableado del circuito principal

YASKAWA SISP YAIL1E 01A YASKAWA Variador CA L1000E Manual técnico

71

In

st

al

ac

n el

éc

tr

ic

a

3

4A0049

R/L1, S/L2, T/L3

16

(6)

16 a 25

(6 a 4)

M6

4 a 6

(35.4 a 53.1)

U/T1, V/T2, W/T3

16

(6)

16 a 25

(6 a 4)

–, +1, +2

16 a 25

(6 a 4)

B1, B2

6.0 a 10

(10 a 8)

M5

2 a 2.5

(17.7 a 22.1)

16

(6)

10 a 16

(8 a 6)

M6

4 a 6

(35.4 a 53.1)

4A0056

R/L1, S/L2, T/L3

25

(4)

6.0 a 50

(10 a 1/0)

M8

9 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

25

(4)

6.0 a 50

(10 a 1/0)

–, +1

16 a 35

(6 a 1)

B1, B2

10 a 16

(8 a 4)

16

(6)

10 a 16

(8 a 6)

4A0075

R/L1, S/L2, T/L3

35

(3)

6.0 a 70

(10 a 3/0)

M8

9 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

35

(3)

6.0 a 70

(10 a 3/0)

–, +1

25 a 35

(4 a 1)

B1, B2

16 a 25

(6 a 3)

16

(6)

16

a 25

(6)

4A0094

R/L1, S/L2, T/L3

35

(2)

16 a 120

(6 a 250)

M8

9 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

50

(1)

16 a 120

(6 a 250)

–, +1

25 a 50

(3 a 1/0)

+3

16 a 50

(6 a 1/0)

25

(4)

16 a 25

(6 a 4)

4A0114

R/L1, S/L2, T/L3

70

(1/0)

16 a 120

(6 a 250)

M8

9 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

70

(1/0)

16 a 120

(6 a 250)

–, +1

25 a 50

(3 a 1/0)

+3

25 a 50

(4 a 1/0)

25

(4)

16 a 25

(6 a 4)

4A0140

R/L1, S/L2, T/L3

95

(3/0)

50 a 95

(1/0 a 4/0)

M10

18 a 23

(159 a 204)

U/T1, V/T2, W/T3

70

(2/0)

50 a 95

(1/0 a 4/0)

–, +1

50 a 95

(1/0 a 4/0)

+3

25 a 95

(3 a 4/0)

25

(4)

25

(4)

Modelo de variador

Terminal

Tamaño del cable

recomendado

mm

2

(AWG, kcmil)

Rango de hilo

mm

2

(AWG, kcmil)

Tamaño de los

tornillos

Torque de apriete

N•m (lb.in)

Advertising