8 cableado del circuito principal – Yaskawa CIMR-AU 200V Manual del usuario

Página 157

Advertising
background image

Modelo de

variador

Terminal

Calibre recomendado

mm

2

(AWG, kcmil)

Rango de cables

mm

2

(AWG, kcmil)

Tamaño de

los tornillos

Torque de ajuste

N·m (lb.in.)

5A0022

R/L1, S/L2, T/L3

10

(8)

6.0 a 16

(10 a 6)

M5

3.6 a 4.0

(31.8 a 35.4)

U/T1, V/T2, W/T3

6.0

(10)

6.0 a 16

(10 a 6)

⊖, ⊕1, ⊕2

6.0 a 16

(10 a 6)

B1, B2

6.0 a 10

(10 a 8)

2.7 a 3.0

(23.9 a 26.6)

10

(8)

6.0 a 10

(10 a 6)

M6

5.4 a 6.0

(47.8 a 53.1)

5A0027
5A0032

R/L1, S/L2, T/L3

16

(6)

16 a 25

(6 a 4)

M6

5.4 a 6.0

(47.8 a 53.1)

U/T1, V/T2, W/T3

16

(6)

16 a 25

(6 a 4)

⊖, ⊕1, ⊕2

16 a 25

(6 a 4)

B1, B2

6.0 a 10

(10 a 8)

M5

2.7 a 3.0

(23.9 a 26.6)

16

(6)

10 a 16

(10 a 6)

M6

5.4 a 6.0

(47.8 a 53.1)

5A0041

R/L1, S/L2, T/L3

16

(6)

6.0 a 25

(10 a 3)

M8

9.0 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

16

(6)

6.0 a 25

(10 a 3)

⊖, ⊕1

(6 a 1)

B1, B2

4.0 a 25

(12 a 3)

16

(6)

10 a 16

(6)

5A0052

R/L1, S/L2, T/L3

25

(4)

6.0 a 25

(10 a 3)

M8

9.0 a 11

(79.7 a 97.4)

U/T1, V/T2, W/T3

16

(6)

6.0 a 25

(10 a 3)

⊖, ⊕1

16 a 35

(6 a 1)

B1, B2

10 a 25

(8 a 3)

16

(6)

10 a 16

(6)

5A0062

R/L1, S/L2, T/L3

25

(4)

6.0 a 95

(10 a 4/0)

M10

18 a 23

(159 a 204)

U/T1, V/T2, W/T3

25

(4)

6.0 a 95

(10 a 4/0)

⊖, ⊕1

25 a 95

(4 a 4/0)

⊕3

16 a 95

(6 a 4/0)

25

(4)

25

(4)

5A0077

R/L1, S/L2, T/L3

25

(3)

6.0 a 95

(10 a 4/0)

M10

18 a 23

(159 a 204)

U/T1, V/T2, W/T3

25

(3)

6.0 a 95

(10 a 4/0)

⊖, ⊕1

25 a 95

(3 a 4/0)

⊕3

16 a 95

(6 a 4/0)

25

(4)

25

(4)

3.8 Cableado del circuito principal

YASKAWA ELECTRIC SISP C710616 41E Variador de CA YASKAWA A1000 Manual Técnico

157

3

Instalación eléctrica

Advertising