Dgc-2020hd gestión de interruptores – Basler Electric DGC-2020HD Manual del usuario
Página 113
Advertising

9469372990 Rev B
103
Mains Breaker
Close Request
Close Mains Breaker
Is
Mains Breaker
Control
enabled?
Mains Breaker
state
Cannot Close
Mains Breaker
No
Yes
Is Load
bus dead?
Is Mains bus
stable?
Perform sync check
P0071-73
Is Load
bus stable?
No
Is Load Bus
metered?
Generator
breaker state
Yes
Open
Cannot Close
Mains Breaker
Is
Generator Bus
stable?
Are buses
synchronized?
Yes
No
No
Yes
No
Yes
Live Bus Close
Enable Setting
Yes
Enabled
Close Mains Breaker
Closed
Open
Yes
No
Disabled
No
Generator
breaker state
Closed
Open
Closed
Figura 45. Diagrama de flujo de condiciones de cierre del disyuntor de la red de alimentación principal
DGC-2020HD
Gestión de Interruptores