Mains Breaker

Close Request

Close Mains Breaker

Is

Mains Breaker

Control

enabled?

Mains Breaker

state

Cannot Close

Mains Breaker

No

Yes

Is Load

bus dead?

Is Mains bus

stable?

Perform sync check

P0071-73

Is Load

bus stable?

No

Is Load Bus

metered?

Generator

breaker state

Yes

Open

Cannot Close

Mains Breaker

Is

Generator Bus

stable?

Are buses

synchronized?

Yes

No

No

Yes

No

Yes

Live Bus Close

Enable Setting

Yes

Enabled

Close Mains Breaker

Closed

Open

Yes

No

Disabled

No

Generator

breaker state

Closed

Open

Closed

Figura 45. Diagrama de flujo de condiciones de cierre del disyuntor de la red de alimentación principal

DGC-2020HD

Gestión de Interruptores