A figura 44 – Basler Electric DGC-2020HD Manual del usuario

Página 111

Advertising
background image

9469372990 Rev B

101

Generator Breaker

Close Request

Close Generator

Breaker

Is Generator

Breaker Control

enabled?

Generator

Breaker

state

Cannot Close

Generator Breaker

No

Yes

Is

Generator Bus

stable?

Synchronize buses

P0071-77

No

Is Mains

bus stable?

No

Mains breaker

state

Yes

Yes

Open

Closed

Is Mains

bus dead?

Is

Generator Bus

stable?

Is

Generator Bus

dead?

Dead Gen Close

Enable setting

Dead Bus Close

Enable setting

Open

No

Yes

Yes

Enabled

Yes

Enabled

Cannot Close

Generator Breaker

No

Disabled

No

Disabled

Close Generator

Breaker

Closed

Figura 44. Diagrama de flujo de condiciones de cierre del disyuntor del generador

(sin la característica opcional Medición de bus de carga)

DGC-2020HD

Gestión de Interruptores