Figura 43 – Basler Electric DGC-2020HD Manual del usuario
Página 109
Advertising

9469372990 Rev B
99
Generator Breaker
Close Request
Close Generator
Breaker
Is Generator
Breaker Control
enabled?
Generator
Breaker
state
Cannot Close
Generator Breaker
No
Yes
Is Load Bus
dead?
Is
Generator Bus
stable?
Synchronize buses
P0071-74
Is
Generator Bus
dead?
Dead Gen Close
Enable setting
No
No
Is Load
Bus stable?
No
Dead Bus Close
Enable setting
Disabled
No
Disabled
Enabled
Yes
Yes
Yes
Enabled
Yes
Open
Closed
Figura 43. Diagrama de flujo de condiciones de cierre del disyuntor del generador
DGC-2020HD
Gestión de Interruptores
Advertising