FoamLogix, Modelo 2.1A y 1.7AHP Clase “A”

Sistemas electrónicos de dosificación de espuma

75

FOAMLOGIX, Model 2.1A Class "A"

73

Electronic Foam Proportioning System

Troubleshooting

ISO 9001 CERTIFIED

NO

NO

1

Continued -

Is Foam Concentrate

being Injected?

Is Correct Amount of

Concentrate Injected?

YES

Proceed with NORMAL

Operation

Verify Calibration

YES

Does Unit Run at FULL

Speed and Shut-Down?

Check LED on Feed-

Back Sensor. Is it ON?

YES

Verify Motor is running

and rotors are turning

Running. Does LED

FLASH?

YES

Is Sensor Adjusted

Correctly?

YES

NO

Remove Connector.

Is 12VDC Available on

PIN-1?

NO

YES

Replace

Harness

Replace

Sensor

NO

Replace Sensor

NO

Adjust Sensor

Chart 44: Hale FoamLogix System Troubleshooting Flow Diagram - continued

Retire el conector. ¿Hay

12 V de CC (ó 24 V de CC

en los sistemas equipados

con 24 V de CC) en la

CLAVIJA-1?

Continuación: ¿Se

está inyectando

el concentrado de

espuma?

Verifique la calibración

Proceda con la

operación NORMAL

Ajuste el sensor

Cambie el sensor

Cambie el

cableado

Cambie el

sensor

NO

NO

NO

NO

NO

NO

Figura 44: Diagrama de flujo de solución de problemas del sistema FoamLogix de

Hale - continuación

¿Es correcta la cantidad de

concentrado inyectado?

¿Funciona la unidad a velocidad

MÁXIMA y se apaga?

Revise el LED en el sensor de

retroalimentación.

¿Está encendido?

Verifique que el motor

esté funcionando y que

los rotores estén girando

cuando funciona. ¿Está

el LED INTERMITENTE?

¿Está el sensor ajustado

correctamente?