Troubleshooting charts, Diagramas de solución de problemas – Class1 FoamLogix2-1A-1-7AHP Manual del usuario
Página 74
FoamLogix, Modelo 2.1A y 1.7AHP Clase “A”
Sistemas electrónicos de dosificación de espuma
74
72
FOAMLOGIX, Model 2.1A Class "A"
Electronic Foam Proportioning System
Troubleshooting
ISO 9001 CERTIFIED
TROUBLESHOOTING CHARTS
Chart 44: Hale FoamLogix System Troubleshooting Flow Diagram
NO
Is Display Lit?
Is Power Available at
Connector C5?
PROVIDE
POWER
Remove C1 from
display. Check for
power at Term/ 1.
Is Power Available?
REPLACE
HARNESS
1
NO
YES
YES
NO
Establish Water Flow
YES
Replace Display
Is Water Flow Value
Displayed?
NO
Is Foam Discharge
OPEN?
OPEN FOAM
DISCHARGE
NO
YES
YES
Check Harness
Connection
OK?
RECONNECT
OR REPLACE
HARNESS
NO
YES
NO
Press ON Button.
Does Motor Run?
NO
Check LEDs on
Controller Box
YES
Verify Water Flow
Sensor Operative.
Is Sensor operating
correctly?
YES
RECONNECT
WATER FLOW
SENSOR
NO
Continued -
See
1 on
next Page.
Is Foam Concentrate
being Injected?
YES
¿Está encendida la
pantalla?
¿Hay energía en el
conector C5?
Cambiar pantalla
¿Está ABIERTA la
descarga de espuma?
ABRA LA
DESCARGA DE
ESPUMA
CAMBIE EL
CABLEADO
SUMINISTRE
ENERGÍA
Revisar las conexiones
del cableado. ¿Están
bien?
VUELVA A
CONECTAR
O CAMBIE EL
CABLEADO
NO
NO
NO
NO
NO
NO
SÍ
SÍ
SÍ
SÍ
NO
NO
NO
SÍ
SÍ
SÍ
SÍ
SÍ
Retire el C1 de la
pantalla. Revise si hay
energía en el Term/1.
¿Hay energía?
Verifique si el sensor
de caudal de agua está
operativo. ¿Funciona
correctamente el
sensor?
VUELVA A CONECTAR
EL SENSOR DE
CAUDAL DE AGUA
Establezca el caudal
de agua
¿Se muestra la válvula
de caudal de agua?
Revise los LED en la
caja del controlador
Figura 44: Diagrama de flujo de solución de problemas del sistema
FoamLogix de Hale
Presione el botón
ENCENDIDO.
¿Funciona el motor?
¿Se está inyectando
el concentrado de
espuma?
Continuación:
Consulte 1
en la página
siguiente
DIAGRAMAS DE SOLUCIÓN DE PROBLEMAS