Flow sensor calibration, Important, Calibración del sensor de caudal – Class1 FoamLogix2-1A-1-7AHP Manual del usuario

Página 54: Importante

Advertising
background image

FoamLogix, Modelo 2.1A y 1.7AHP Clase “A”

Sistemas electrónicos de dosificación de espuma

54

52

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Installation

ISO 9001 CERTIFIED

FLOW SENSOR CALIBRATION

Verify flow sensor calibration during NFPA/UL

testing of the apparatus and delivery to end user.

IMPORTANT!

AN ACCURATE FLOW MEASURING DEVICE MUST

BE USED TO MEASURE THE WATER FLOW WHEN

CALIBRATING THE FLOW SENSOR. USE A

SUITABLE SIZE, SMOOTH BORE, NOZZLE AND AN

ACCURATE AND CALIBRATED PITOT GAUGE

INSTRUMENT. HAND HELD PITOT GAUGES ARE

USUALLY NOT VERY ACCURATE.

MAKE SURE THE SYSTEM IS CALIBRATED WITH

AN ACCURATE FLOW MEASURING DEVICE.

1. Determine the water flow normally ex-

pected from the discharge outlet and

establish flow.

2. Make sure the water flow established is

within the range of the flow sensor moni-

toring the discharge.

For example, establish a flow rate of 150

GPM (568 LPM) of water through a nozzle

and Pitot system. Compare the calculated

flow value to the value shown on the

control unit display.

Figure 26: Display - Password and Calibration Modes

SELECT DISPLAY

Press and

HOLD

Continued to

HOLD

Displayed when

 is pressed

Pressed in

sequence to

enter passwords

Displayed when

is pressed

Release when

CAL is shown

Figure 27: Display - Flow Sensor Calibration

Suelte cuando

se muestra CAL

Presione en

secuencia para

ingresar las

contraseñas

Mantenga

PRESIONADO

Se muestra cuando

se presiona

Se muestra cuando

se presiona

SELECCIONE

LA PANTALLA,

presione y

MANTENGA

PRESIONADO

Figura 26: Pantalla - Contraseña

y modos de calibración

52

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Installation

ISO 9001 CERTIFIED

FLOW SENSOR CALIBRATION

Verify flow sensor calibration during NFPA/UL

testing of the apparatus and delivery to end user.

IMPORTANT!

AN ACCURATE FLOW MEASURING DEVICE MUST

BE USED TO MEASURE THE WATER FLOW WHEN

CALIBRATING THE FLOW SENSOR. USE A

SUITABLE SIZE, SMOOTH BORE, NOZZLE AND AN

ACCURATE AND CALIBRATED PITOT GAUGE

INSTRUMENT. HAND HELD PITOT GAUGES ARE

USUALLY NOT VERY ACCURATE.

MAKE SURE THE SYSTEM IS CALIBRATED WITH

AN ACCURATE FLOW MEASURING DEVICE.

1. Determine the water flow normally ex-

pected from the discharge outlet and

establish flow.

2. Make sure the water flow established is

within the range of the flow sensor moni-

toring the discharge.

For example, establish a flow rate of 150

GPM (568 LPM) of water through a nozzle

and Pitot system. Compare the calculated

flow value to the value shown on the

control unit display.

Figure 26: Display - Password and Calibration Modes

SELECT DISPLAY

Press and

HOLD

Continued to

HOLD

Displayed when

 is pressed

Pressed in

sequence to

enter passwords

Displayed when

is pressed

Release when

CAL is shown

Figure 27: Display - Flow Sensor Calibration

Figura 27: Pantalla - Calibración del sensor de caudal

CALIBRACIÓN DEL SENSOR DE CAUDAL

Verifique la calibración del sensor de caudal durante

la prueba según la NFPA/UL del aparato y entrega

al usuario final.

¡IMPORTANTE!

SE DEBE USAR UN DISPOSITIVO DE MEDICIÓN

PRECISO DE CAUDAL PARA MEDIR EL CAUDAL

DE AGUA CUANDO SE CALIBRE EL SENSOR

DE CAUDAL. USE UNA BOQUILLA DE TAMAÑO

APROPIADO Y DE PARED INTERIOR LISA Y UN

INSTRUMENTO DE MEDICIÓN PITOT PRECISO Y

CALIBRADO. LOS MEDIDORES PORTÁTILES PITOT

GENERALMENTE NO SON MUY PRECISOS.

ASEGÚRESE DE QUE EL SISTEMA ESTÉ

CALIBRADO CON UN DISPOSITIVO PRECISO DE

MEDICIÓN DE CAUDAL.

Determine el caudal de agua que normalmente

1.

se espera desde la salida de descarga y fije el

caudal.
Asegúrese de que el caudal de agua establecido

2.

esté dentro del rango del sensor de caudal que

monitorea la descarga.

Por ejemplo, fije un caudal de 568 LPM (150

GPM) de agua a través de una boquilla y un

sistema Pitot. Compare el valor de caudal

calculado con el valor mostrado en la pantalla de

la unidad de control.