50

900-0112-02-00 Rev A

Tabla 22 Configuraciones del inversor de 48 voltios (MATE3)

Campo

Punto

Predeterminado

Mínimo

Máximo

Sensitivity (consulte la página 12 para
conocer los incrementos)

6

0

50

Pulse Length

8

4

20

Search

Pulse Spacing

Ciclos de 60 CA

Ciclos de 4 CA

Ciclos de 120 CA

Input Type

Grid

Grid o Gen

Input Support

Y

Y o N

Grid Input AC Limit

25 ACA

2,5 ACA

30 ACA

Gen Input AC Limit

25 ACA

2,5 ACA

30 ACA

AC Input and
Current Limit

Charger AC Limit

5,5 ACA

0 ACA

6 ACA

AC1/Grid Lower Limit

208 VCA

140 VCA

220 VCA

AC1/Grid Upper Limit

252 VCA

250 VCA

280 VCA

Grid AC Input
Voltage Limits

AC1/Grid Transfer Delay

Ciclos de 6 CA

Ciclos de 0 CA

Ciclos de 240 CA

LowerVoltage Limit

208 VCA

140 VCA

220 VCA

Upper Voltage Limit

252 VCA

250 VCA

280 VCA

Transfer Delay

Ciclos de 60 CA

Ciclos de 0 CA

Ciclos de 240 CA

Gen AC Input
Voltage Limits

Connect Delay

0,5 minutos

0,2 minutos

15 minutos

AC Output

AC Output

230 VCA

210 VCA

250 VCA

Cut-Out Voltage

42 VCC

36 VCC

48 VCC

Low Battery

Cut-In Voltage

50 VCC

40 VCC

56 VCC

Absorb Voltage

57,6 VCC

52 VCC

64 VCC

(Absorb) Time

1,0 horas

0,0 horas

24,0 horas

Float Voltage

54,4 VCC

48 VCC

60 VCC

(Float) Time

1,0 horas

0,0 horas

24,0 horas

Battery
Charger

Re-Float Voltage

50 VCC

48 VCC

26 VCC

Equalize Voltage

58,4 VCC

56 VCC

68 VCC

Battery
Equalize

(Equalize) Time

1,0 horas

0,0 horas

24,0 horas

Aux Mode

Cool Fan

Remote, Load Shed, Gen Alert, Fault, Vent

Fan, Cool Fan, Divert DC, Divert AC, o AC Drop

(Load Shed) Enable Voltage

44 VCC

40 VCC

56 VCC

(Gen Alert) ON Voltage

44 VCC

40 VCC

56 VCC

(Gen Alert ON) Delay

4 minutos

0 minutos

240 minutos

(Gen Alert) OFF Voltage

56 VCC

48 VCC

72 VCC

(Gen Alert OFF) Delay

9 minutos

0 minutos

240 minutos

(Vent Fan) Enable Voltage

52 VCC

40 VCC

64 VCC

(Vent Fan) Off Period

5 minutos

0 minutos

30 minutos

(Divert DC or AC) Enable Voltage

58,4 VCC

48 VCC

64 VCC

Auxiliary
Output

(Divert DC or AC) Off Delay

30 segundos

0 segundos

240 segundos

Inverter
Stacking

Stack Mode

Master

Master, OB Slave L1, 3p Classic B , 3p Classic C

Master Adjust Only

0

0

7

Power Save

Slave Adjust Only

1

1

15

Grid Tie Enable

Y

Y o N

Sell Voltage

47,2 VCC

40 VCC

60 VCC

Grid-Tie Sell

Grid Tie Window

IEEE

IEEE o user

Input Voltage

12

-1 VCA

-3 VCA

1 VCA

Output Voltage

12

-1 VCA

-3 VCA

1 VCA

Calibrate

Battery Voltage

13

0,0 VCC

-0,8 VCC

0,8 VCC


12

Estos valores representan una configuración ajustable con un rango total de 4 VCA. El valor predeterminado de -1 significa que la calibración restará 1 voltio

del valor medido. El rango de las configuraciones permite que se añada hasta 1 voltio al valor medido, o que se resten hasta 3 voltios. El resultado también
se muestra.

13

Estos valores representan una configuración ajustable con un rango de ± 0,4 VCC desde el valor medido. El rango de las configuraciones permite que hasta se

añadan o resten 0,4 voltios del valor medido (en incrementos de 0,2 VCC). El resultado también se muestra.