Especificaciones – Outback Power Systems GFX International Series Operators Manual Manual del usuario

Página 51

Advertising
background image

Especificaciones

900-0112-02-00 Rev A

49

Tabla 21 Configuraciones del inversor de 24 voltios (MATE3)

Campo

Punto

Predeterminado

Mínimo

Máximo

Sensitivity (consulte la página 12 para
conocer los incrementos)

6

0

50

Pulse Length

8

4

20

Search

Pulse Spacing

Ciclos de 60 CA

Ciclos de 4 CA

Ciclos de 120 CA

Input Type

Grid

Grid o Gen

Input Support

Y

Y o N

Grid Input AC Limit

25 ACA

2,5 ACA

30 ACA

Gen Input AC Limit

25 ACA

2,5 ACA

30 ACA

AC Input and
Current Limit

Charger AC Limit

5,5 ACA

0 ACA

6 ACA

LowerVoltage Limit

208 VCA

140 VCA

220 VCA

Upper Voltage Limit

252 VCA

250 VCA

280 VCA

Grid AC Input
Voltage Limits

Transfer Delay

Ciclos de 6 CA

Ciclos de 0 CA

Ciclos de 240 CA

LowerVoltage Limit

208 VCA

140 VCA

220 VCA

Upper Voltage Limit

252 VCA

250 VCA

280 VCA

Transfer Delay

Ciclos de 6 CA

Ciclos de 0 CA

Ciclos de 240 CA

Gen AC Input
Voltage Limits

Connect Delay

0,5 minutos

0,2 minutos

15 minutos

AC Output

AC Output

230 VCA

210 VCA

250 VCA

Cut-Out Voltage

21 VCC

18 VCC

24 VCC

Low Battery

Cut-In Voltage

25 VCC

20 VCC

28 VCC

Absorb Voltage

28,8 VCC

26 VCC

32 VCC

(Absorb) Time

1,0 horas

0,0 horas

24,0 horas

Float Voltage

27,2 VCC

24 VCC

30 VCC

(Float) Time

1,0 horas

0,0 horas

24,0 horas

Battery
Charger

Re-Float Voltage

25 VCC

24 VCC

26 VCC

Equalize Voltage

29,2 VCC

28 VCC

34 VCC

Battery
Equalize

(Equalize) Time

1,0 horas

0,0 horas

24,0 horas

Aux Mode

Cool Fan

Remote, Load Shed, Gen Alert, Fault, Vent

Fan, Cool Fan, Divert DC, Divert AC, o AC Drop

(Load Shed) Enable Voltage

22 VCC

20 VCC

28 VCC

(Gen Alert) ON Voltage

22 VCC

20 VCC

28 VCC

(Gen Alert ON) Delay

4 minutos

0 minutos

240 minutos

(Gen Alert) OFF Voltage

28 VCC

24 VCC

36 VCC

(Gen Alert OFF) Delay

9 minutos

0 minutos

240 minutos

(Vent Fan) Enable Voltage

26 VCC

20 VCC

32 VCC

(Vent Fan) Off Period

5 minutos

0 minutos

30 minutos

(Divert DC or AC) Enable Voltage

29,2 VCC

24 VCC

32 VCC

Auxiliary
Output

(Divert DC or AC) Off Delay

30 segundos

0 segundos

240 segundos

Inverter
Stacking

Stack Mode

Master

Master, OB Slave L1, 3p Classic B , 3p Classic C

Master Adjust Only

0

0

7

Power Save

Slave Adjust Only

1

1

15

Grid Tie Enable

Y

Y o N

Sell Voltage

23,6 VCC

20 VCC

30 VCC

Grid-Tie Sell

Grid Tie Window

IEEE

IEEE o user

Input Voltage

10

-1 VCA

-3 VCA

1 VCA

Output Voltage

10

-1 VCA

-3 VCA

1 VCA

Calibrate

Battery Voltage

11

0,0 VCC

-0,4 VCC

0,4 VCC

10

Estos valores representan una configuración ajustable con un rango total de 4 VCA. El valor predeterminado de -1 significa que la calibración restará 1 voltio

del valor medido. El rango de las configuraciones permite que se añada hasta 1 voltio al valor medido, o que se resten hasta 3 voltios. El resultado también
se muestra.

11

Estos valores representan una configuración ajustable con un rango de ± 0,4 VCC desde el valor medido. El rango de las configuraciones permite que hasta se

añadan o resten 0,4 voltios del valor medido (en incrementos de 0,2 VCC). El resultado también se muestra.