Especificaciones – Outback Power Systems GFX International Series Operators Manual Manual del usuario
Página 49

Especificaciones
900-0112-02-00 Rev A
47
Tabla 19 Configuraciones del inversor de 24 voltios (MATE)
Campo
Punto
Predeterminado
Mínimo
Máximo
Search Sensitivity (consulte la página 12 para
conocer los incrementos)
6
0
50
Search Pulse Length
8
4
20
Search
Search Pulse Spacing
Ciclos de 60 CA
Ciclos de 4 CA
Ciclos de 120 CA
AC Transfer Control
Grid
Grid o Gen
AC1/Grid Limit
25 ACA
2,5 ACA
30 ACA
Input
AC2/Gen Limit
25 ACA
2,5 ACA
30 ACA
Low Battery Cut-Out (LBCO)
21 VCC
18 VCC
24 VCC
Low Battery Cut-In (LBCI)
25 VCC
20 VCC
28 VCC
Inverter
Adjust Output Voltage
230 VCA
210 VCA
250 VCA
Charger Limit
5,5 ACA
0 ACA
6 ACA
Absorb Voltage
28,8 VCC
26 VCC
32 VCC
Absorb Time Limit
1,0 horas
0,0 horas
24,0 horas
Float Voltage
27,2 VCC
24 VCC
30 VCC
Float Time Period
1,0 horas
0,0 horas
24,0 horas
ReFloat Voltage
25 VCC
24 VCC
26 VCC
Equalization Voltage
29,2 VCC
28 VCC
34 VCC
Charger
Equalization Time Period
1,0 horas
0,0 horas
24,0 horas
AC1/Grid Lower Limit
208 VCA
140 VCA
220 VCA
AC1/Grid Upper Limit
252 VCA
250 VCA
280 VCA
Grid
AC1/Grid Transfer Delay
Ciclos de 6 CA
Ciclos de 0 CA
Ciclos de 240 CA
Gen Input Connect Delay
0,5 minutos
0,2 minutos
15 minutos
AC2/Gen Lower Limit
208 VCA
140 VCA
220 VCA
AC2/GenUpper Limit
252 VCA
250 VCA
280 VCA
AC2/Gen Transfer Delay
Ciclos de 6 CA
Ciclos de 0 CA
Ciclos de 240 CA
Generator
(Gen)
AC2/Gen Support
ON
ON o OFF
AUX Output Control
AUTO
AUX Output Function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent
Fan, Fault, GenAlert, LoadShed, o Remote
GenAlert On Voltage
44 VCC
40 VCC
56 VCC
GenAlert On Delay
4 minutos
0 minutos
240 minutos
GenAlert Off Set Point
56 VCC
48 VCC
72 VCC
GenAlert Off Delay
9 minutos
0 minutos
240 minutos
Load Shed Off Voltage
44 VCC
40 VCC
56 VCC
Vent Fan On Set Point
52 VCC
40 VCC
64 VCC
Vent Fan Off Period
5 minutos
0 minutos
30 minutos
Diversion On Voltage
58,4 VCC
48 VCC
64 VCC
Auxiliary
(AUX)
Diversion Off Delay
30 segundos
0 segundos
240 segundos
Stacking
Stack Phase
Master
Master, OB Slave L1, 3p Classic B, 3p Classic C
Master Adjust Only
0
0
7
Power Save
Slave Adjust Only
1
1
15
Sell RE Volts
52 VCC
40 VCC
60 VCC
Grid Tie Window
User
IEEE o User
Sell
Grid Tie Authority
GridTie
GridTie o No Sell
Vac Input Adjustment
6
236 VCA
220 VCA
254 VCA
Vac Output Adjustment
6
236 VCA
220 VCA
254 VCA
Calibration
(Cal)
Battery Vdc Adjustment
7
2 VCC
0 VCC
4 VCC
6
Estos valores representan una configuración ajustable con un rango total de 4 VCA. El valor predeterminado de -1 significa que la calibración restará 1 voltio al
valor medido. El rango de las configuraciones permite que se añada hasta 1 voltio al valor medido, o que se resten hasta 3 voltios. El resultado también
se muestra.
7
Estos valores representan una configuración ajustable con un rango de ± 0,2 VCC desde el valor medido. El rango de las configuraciones permite que se añadan
o resten hasta 0,2 voltios al valor medido. El resultado también se muestra.