Especificaciones

900-0112-02-00 Rev A

47

Tabla 19 Configuraciones del inversor de 24 voltios (MATE)

Campo

Punto

Predeterminado

Mínimo

Máximo

Search Sensitivity (consulte la página 12 para
conocer los incrementos)

6

0

50

Search Pulse Length

8

4

20

Search

Search Pulse Spacing

Ciclos de 60 CA

Ciclos de 4 CA

Ciclos de 120 CA

AC Transfer Control

Grid

Grid o Gen

AC1/Grid Limit

25 ACA

2,5 ACA

30 ACA

Input

AC2/Gen Limit

25 ACA

2,5 ACA

30 ACA

Low Battery Cut-Out (LBCO)

21 VCC

18 VCC

24 VCC

Low Battery Cut-In (LBCI)

25 VCC

20 VCC

28 VCC

Inverter

Adjust Output Voltage

230 VCA

210 VCA

250 VCA

Charger Limit

5,5 ACA

0 ACA

6 ACA

Absorb Voltage

28,8 VCC

26 VCC

32 VCC

Absorb Time Limit

1,0 horas

0,0 horas

24,0 horas

Float Voltage

27,2 VCC

24 VCC

30 VCC

Float Time Period

1,0 horas

0,0 horas

24,0 horas

ReFloat Voltage

25 VCC

24 VCC

26 VCC

Equalization Voltage

29,2 VCC

28 VCC

34 VCC

Charger


Equalization Time Period

1,0 horas

0,0 horas

24,0 horas

AC1/Grid Lower Limit

208 VCA

140 VCA

220 VCA

AC1/Grid Upper Limit

252 VCA

250 VCA

280 VCA

Grid

AC1/Grid Transfer Delay

Ciclos de 6 CA

Ciclos de 0 CA

Ciclos de 240 CA

Gen Input Connect Delay

0,5 minutos

0,2 minutos

15 minutos

AC2/Gen Lower Limit

208 VCA

140 VCA

220 VCA

AC2/GenUpper Limit

252 VCA

250 VCA

280 VCA

AC2/Gen Transfer Delay

Ciclos de 6 CA

Ciclos de 0 CA

Ciclos de 240 CA

Generator
(Gen)

AC2/Gen Support

ON

ON o OFF

AUX Output Control

AUTO

AUX Output Function

Cool Fan

Cool Fan, DivertDC, DivertAC, AC Drop, Vent

Fan, Fault, GenAlert, LoadShed, o Remote

GenAlert On Voltage

44 VCC

40 VCC

56 VCC

GenAlert On Delay

4 minutos

0 minutos

240 minutos

GenAlert Off Set Point

56 VCC

48 VCC

72 VCC

GenAlert Off Delay

9 minutos

0 minutos

240 minutos

Load Shed Off Voltage

44 VCC

40 VCC

56 VCC

Vent Fan On Set Point

52 VCC

40 VCC

64 VCC

Vent Fan Off Period

5 minutos

0 minutos

30 minutos

Diversion On Voltage

58,4 VCC

48 VCC

64 VCC

Auxiliary
(AUX)

Diversion Off Delay

30 segundos

0 segundos

240 segundos

Stacking

Stack Phase

Master

Master, OB Slave L1, 3p Classic B, 3p Classic C

Master Adjust Only

0

0

7

Power Save

Slave Adjust Only

1

1

15

Sell RE Volts

52 VCC

40 VCC

60 VCC

Grid Tie Window

User

IEEE o User

Sell

Grid Tie Authority

GridTie

GridTie o No Sell

Vac Input Adjustment

6

236 VCA

220 VCA

254 VCA

Vac Output Adjustment

6

236 VCA

220 VCA

254 VCA

Calibration
(Cal)

Battery Vdc Adjustment

7

2 VCC

0 VCC

4 VCC

6

Estos valores representan una configuración ajustable con un rango total de 4 VCA. El valor predeterminado de -1 significa que la calibración restará 1 voltio al

valor medido. El rango de las configuraciones permite que se añada hasta 1 voltio al valor medido, o que se resten hasta 3 voltios. El resultado también
se muestra.

7

Estos valores representan una configuración ajustable con un rango de ± 0,2 VCC desde el valor medido. El rango de las configuraciones permite que se añadan

o resten hasta 0,2 voltios al valor medido. El resultado también se muestra.

Advertising