Diagrama de flujo del proceso de alineación – Fire Fighting Enterprises FIRERAY 100R Manual del usuario
Página 6

Amber
Constant
AMBER
Red
Red
Amber
Neither
Diagrama de Flujo del Proceso de Alineación:
Wait until both LED’s stop
flashing (up to 30 seconds)
Return to Prism
Targeting Mode
Slowly turn the
thumbwheel in the
same direction
Reverse the
direction of the
thumbwheel
Exit Alignment Mode
and enter Operating
Mode
Select alignment mode AMBER
LED will illuminate for
5 seconds
LED
flashing?
Slowly adjust a thumbwheel in one
direction and observe the LEDs
LED
flashing?
For optimum alignment,
deflection of the beam in all
four planes should cause the
Amber LED to flash first
Repeat the
process for the
other
thumbwheel
Both
thumbwheels
adjusted?
No
Yes
Stop turning the
thumbwheel and wait
for the Red LED to
stop flashing
Stop turning the
thumbwheel
Seleccione el Modo alineación,
el LED ÁMBAR se iluminará
durante 5 segundos.
Espere hasta que ambos
LED dejen de parpadear
(hasta 30 segundos)
Ajuste lentamente una rueda
dentada en una dirección y
observe los LED.
ÁMBAR
Fijo
Vuelva al Modo
Prisma Objetivo
Deje de girar la rueda
dentada y espere a que el
LED rojo deje de
parpadear
Gire lentamente la
rueda dentada en la
misma dirección
parpadeando?
Ámbar
Rojo
Invierta la
dirección de la
rueda dentada
Ninguno de los dos
Deje de girar la rueda
dentada
Repita el
proceso para la
otra rueda
dentada
ajustadas?
Sí
Para la alineación óptima, la
desviación del haz en los
cuatro planos debe hacer
que el LED ámbar parpadee
en primer lugar
¿LED
Ámbar
Rojo
Salga del Modo de
Alineación y entre en
el Modo de
Funcionamiento
parpadeando?
¿LED
¿Ambas
Ruedas dentadas