Set receive to transmit delay, Report number of floats, Report receive to transmit delay – VEGA VEGABAR 83 Modbus and Levelmaster protocol - Operating Instructions Manual del usuario
Página 80

80
10 Anexo
VEGABAR 83 • Protocolo Modbus y Levelmaster
46295-ES-131120
Response:
Parámetro
Length
Code/Data
Set Baud Rate
11 characters ASCII
Ejemplo: U01B9600E71
Cambiar equipo en la dirección 1 a la tasa de baudios 9600, paridad par, 7 bits de datos, 1 bit de
parada
Set Receive to Transmit Delay
Request:
Parámetro
Length
Code/Data
Set Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Parámetro
Length
Code/Data
Set Receive to Transmit Delay
6 characters ASCII
UuuROK
Report Number of Floats
Request:
Parámetro
Length
Code/Data
Set Receive to Transmit Delay
4 characters ASCII
UuuF
Response:
Parámetro
Length
Code/Data
Set Receive to Transmit Delay
5 characters ASCII
UuuFn
n = number of measurement values
(0, 1 or 2)
Report Receive to Transmit Delay
Request:
Parámetro
Length
Code/Data
Report Receive to Transmit Delay
4 characters ASCII
UuuR
Response:
Parámetro
Length
Code/Data
Report Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms