Bloques de funcionamiento – VEGA VEGAFLEX 81 Foundation Fieldbus Coax probe Manual del usuario
Página 77

77
11 Anexo
VEGAFLEX 81 • Foundation Fieldbus
44215-ES-130925
Electricial Characteristics
Physicial Layer Type
Low-power signaling,
bus-powered, FISCO I.S.
Input Impedance
> 3000 Ohms between
7.8 KHz - 39 KHz
Unbalanced Capacitance
< 250 pF to ground from either
input terminal
Output Amplitude
0.8 V P-P
Electrical Connection
2 Wire
Polarity Insensitive
Yes
Max. Current Load
10 mA
Device minimum operating voltage
9 V
Transmitter Function Blocks
Resource Block (RB)
1
Transducer Block (TB)
1
Standard Block (AI)
3
Execution Time
30 mS
Advanced Function Blocks
Discret Input (DI)
Yes
PID Control
Yes
Output Splitter (OS)
Yes
Signal Characterizer (SC)
Yes
Integrator
Yes
Input Selector (IS)
Yes
Arithmetic (AR)
Yes
Diagnostics
Standard
Yes
Advanced
Yes
Performance
No
Function Blocks Instantiable
No
General Information
LAS (Link Active Scheduler)
Yes
Master Capable
Yes
Number of VCRs (Virtual Communication Re-
lationships)
24
Bloques de funcionamiento
Transducer Block (TB)
El Transducer Block "Analog Input (AI)" toma el valor de medición original (Secondary Value 2),
realiza el ajuste min.-/max. (Secondary Value 1), hace una linalización (Primary Value) y pone los
valores a disposición en su salida para otros bloques funcionales.