4 modbus instrucciones rtu, Fc3 read holding register – VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Manual del usuario
Página 74

74
10 Anexo
VEGAPULS 62 • Protocolo Modbus y Levelmaster
41362-ES-121113
Register Name
Register Number
Type
Note
SV
2104
DWord
Secondary Variable in Byte-Reihenfolge DCBA (Litt-
le Endian)
TV
2106
DWord
Third Variable in Byte-Reihenfolge ABCD DCBA (Litt-
le Endian)
QV
2108
DWord
Quarternary Variable in Byte-Reihenfolge DCBA (Litt-
le Endian)
Status
2200
DWord
See Register 100
PV
2202
DWord
Primary Variable in Byte Order BACD (Middle Endian)
SV
2204
DWord
Secondary Variable in Byte Order BACD (Middle En-
dian)
TV
2206
DWord
Third Variable in Byte Order BACD (Middle Endian)
QV
2208
DWord
Quarternary Variable in Byte Order BACD (Middle En-
dian)
Unit Codes for Register 104, 108, 112, 116
Unit Code
Measurement Unit
32
Degree Celsius
33
Degree Fahrenheit
40
US Gallon
41
Liters
42
Imperial Gallons
43
Cubic Meters
44
Feet
45
Meters
46
Barrels
47
Inches
48
Centimeters
49
Millimeters
111
Cubic Yards
112
Cubic Feet
113
Cubic Inches
10.4 Modbus instrucciones RTU
FC3 Read Holding Register
Con esa instrucción se puede leer una cantidad arbitraria (1-127) en los registros holding. Se trans-
miten el registro inicial, desde el que hay que leer y la cantidad de registros.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03