VEGA VEGABAR 54 Foundation Fieldbus - climate compensated Manual del usuario

Página 60

Advertising
background image

60

10 Anexo

VEGABAR 54 • Fundación Fielbus - con compensación climática

36791-ES-130416

– Highest calibrated value. For calibration of the high limit point you give the high measurement

value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_POINT_LO

– Lowest calibrated value. For calibration of the low limit point you give the low measurement

value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives

from 'Sensor_range.unit'

CAL_MIN_SPAN

– Minimum calibration span value allowed. Necessary to ensure that when calibration is done,

the two calibrated points (high and low) are not too close together. Unit derives from 'Sen-

sor_range.unit'

SCALE_IN

– Min/max-adjustment: Upper and lower calibrated points of the sensor. Unit derives from 'Sen-

sor_range.unit'

trimmed_value

– Sensor value after the trim processing. Unit derives from 'Sensor_range.unit'

sensor_sn

– Sensor serial number

temperature

– Process temperature. Selected as input to AIFB by setting 'Channel' = 4. Unit derives from

'Temperature.unit'

temperature_unit

– Unit code of 'Temperature', 'Max/Min_peak_temperature_value'

– °C, °F, K, °R

max_peak_temperature_value

– Holds the maximum process temperature. Write access resets to current value. Unit derives

from 'Temperature.unit'

– Write access resets to current value

min_peak_temperature_value

– Holds the minimum process temperature. Write access resets to current value. Unit derives

from 'Temperature.unit'

– Write access resets to current value

10.3 Dimensiones

Los dibujos acotados siguientes representan solo una parte de las versiones posibles. Dibujos

acotados detallados se pueden descargar de www.vega.com en "Downloads" y "Dibujos".
La carcasa de dos cámara no están disponibles para equipos con señal de salida 4 … 20 mA

Advertising