cal_level_lo

- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit is

defined in "level_unit".

-

When writing "cal_level_lo" and "cal_type" = 1, the "Calibration Lowest Point" is

automatically set to "sensor_value".

l

cal_type

- Min./Max. adjustment: this parameter defines the type of calibration:

- Dry: no influence of "sensor_value" on level calibration

-

Online: current "sensor_value"determines "Calibration Highest/Lowest Point".

l

level

l

level_unit

l

level_offset

l

end_of_operation_range

l

begin_of_operation_range

l

product_type

-

set up to suit the process conditions

l

liquids_medium_type

-

set up to suit the process conditions

l

solids_medium_type

-

set up to suit the process conditions

l

liquids_vessel_type

-

set up to suit the process conditions

l

solids_vessel_type

-

set up to suit the process conditions

l

fast_level_change

-

set up to suit the process conditions

l

first_echo_factor

l

pulse_velocity_correction

l

echo_quality

l

empty_vessel_curve_corr_dist

- The actual distance from sensor to the product surface must be entered before creating

a false echo memory.

-

The unit is defined in "sensor_range.Units Index".

l

empty_vessel_curve_corr_op_code

-

Create a false echo memory. Selectable codes are: update, create new and delete.

l

sound_velocity

l

sound_velocity_unit

l

Temperatura

-

Value of the temperature. The unit is defined in "temperature_unit"

l

temperature_unit

-

Selects the unit of "temperature", "max/min_peak_temperature_value"