l
cal_level_lo
- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit is
defined in "level_unit".
-
When writing "cal_level_lo" and "cal_type" = 1, the "Calibration Lowest Point" is
automatically set to "sensor_value".
l
cal_type
- Min./Max. adjustment: this parameter defines the type of calibration:
- Dry: no influence of "sensor_value" on level calibration
-
Online: current "sensor_value"determines "Calibration Highest/Lowest Point".
l
level
l
level_unit
l
level_offset
l
end_of_operation_range
l
begin_of_operation_range
l
product_type
-
set up to suit the process conditions
l
liquids_medium_type
-
set up to suit the process conditions
l
solids_medium_type
-
set up to suit the process conditions
l
liquids_vessel_type
-
set up to suit the process conditions
l
solids_vessel_type
-
set up to suit the process conditions
l
fast_level_change
-
set up to suit the process conditions
l
first_echo_factor
l
pulse_velocity_correction
l
echo_quality
l
empty_vessel_curve_corr_dist
- The actual distance from sensor to the product surface must be entered before creating
a false echo memory.
-
The unit is defined in "sensor_range.Units Index".
l
empty_vessel_curve_corr_op_code
-
Create a false echo memory. Selectable codes are: update, create new and delete.
l
sound_velocity
l
sound_velocity_unit
l
Temperatura
-
Value of the temperature. The unit is defined in "temperature_unit"
l
temperature_unit
-
Selects the unit of "temperature", "max/min_peak_temperature_value"
Anexo
VEGASON 66 - Foundation Fieldbus
57