VEGA VEGABAR 86 Modbus and Levelmaster protocol - Operating Instructions Manual del usuario

Página 66

Advertising
background image

66

10 Anexo

VEGABAR 86 • Protocolo Modbus y Levelmaster

46296-ES-131120

Register Name

Register Number

Type

Note

QV

1438

Quarternary Variable in Byte Order CDAB

Status

2000

DWord

See Register 100

PV

2002

DWord

Primary Variable in Byte Order ABCD (Big Endian)

SV

2004

DWord

Secondary Variable in Byte Order ABCD (Big Endian)

TV

2006

DWord

Third Variable in Byte Order ABCD (Big Endian)

QV

2008

DWord

Quarternary Variable in Byte Order ABCD (Big En-

dian)

Status

2100

DWord

See Register 100

PV

2102

DWord

Primary Variable in Byte Order DCBA (Little Endian)

SV

2104

DWord

Secondary Variable in Byte Order DCBA (Little En-

dian)

TV

2106

DWord

Third Variable in Byte Order ABCD DCBA (Little En-

dian)

QV

2108

DWord

Quarternary Variable in Byte Order DCBA (Little En-

dian)

Status

2200

DWord

See Register 100

PV

2202

DWord

Primary Variable in Byte Order BACD (Middle Endian)

SV

2204

DWord

Secondary Variable in Byte Order BACD (Middle En-

dian)

TV

2206

DWord

Third Variable in Byte Order BACD (Middle Endian)

QV

2208

DWord

Quarternary Variable in Byte Order BACD (Middle En-

dian)

Unit Codes for Register 104, 108, 112, 116

Unit Code

Measurement Unit

32

Degree Celsius

33

Degree Fahrenheit

40

US Gallon

41

Liters

42

Imperial Gallons

43

Cubic Meters

44

Feet

45

Meters

46

Barrels

47

Inches

48

Centimeters

49

Millimeters