10

thermostatic expansion valve location

This device is located on the same side as the refrigeration

stub. An Alco balanced port expansion valve model

is furnished as standard equipment, unless otherwise

specified by customer.
expansion valve adjustment
Expansion valves must be adjusted to fully feed the

evaporator. Before attempting any adjustments, make

sure the evaporator is either clear or very lightly covered

with frost, and that the fixture is within 10°F of its expected

operating temperature.
Measuring the operating superheat

1. Determine the suction pressure with an accurate

pressure gauge at the evaporator outlet.

. From a refrigerant pressure temperature chart,

determine the saturation temperature at the

observed suction pressure.

3. Measure the temperature of the suction gas at the

thermostatic remote bulb location.

4. Subtract the saturation temperature obtained in step

No.  from the temperature measured in step No. 3.

5. The difference is superheat.

6. Set the superheat for 5°F - 7°F.

t-stat location

Thermostats are located within the electrical raceway.

The raceway location is dependent on the style of the

front panel and whether the case is going to be pushed

up against a wall.

Front of Case

Ballast location

Ballast and T-stat are located in the front right hand area

of the case, viewed from customer angle.
In all cases, the thermostat is located on the same side of

the case. If you are looking at the case from the front, it is

the right-hand side. If you are looking at the case from the

back, it is the left-hand side.

It is the contractor’s responsibility to install

case(s) according to local construction and

health codes.

refrigeration (Cont'd)