INSTALLATION

6

YORK INTERNATIONAL

FORM 115.20-NOM2 (105)

7

YORK INTERNATIONAL

INSTALLATION

FORM 115.20-NOM2 (105)

VALVE CLUSTER

2-Way Motorized Valve Assemblies
1. The motorized valve assembly should be attached to

the supply header, which is the connection nearest

the air outlet flange on the unit.

2. Prior to soldering the joints, operate all the hand

valves to ensure that the handles will fully open and

close without interference to other valves, ceiling,

wall, plenum or other accessories.

3. All valves will operate at any angle with the excep-

tion of the motorized valve, which must be installed

with the power head above horizontal. The actuator

box requires a 3/4" clearance for removal.

3-Way Motorized Valve Assembly
1. The 3-way valve assemblies will mount to the

coil in only one position. On four-pipe right hand

systems, a "B" valve assembly is required for the

chilled water connection and an "A" valve assembly

is required for the hot water connection. On left

hand systems, an "A" valve assembly is required

for the chilled water connection and the hot water

connection. (See figure 4.)

2. Prior to soldering the joints, operate all the hand

valves to ensure that the handles will fully open and

close without interference to other valves, ceiling,

wall, plenum or other accessories.

3. All valves will operate at any angle with the excep-

tion of the motorized valve, which must be installed

with the power head above horizontal. The actuator

box requires a 3/4" clearance for removal.

FIG. 5 – 3 WAY MOTORIZED VALVE ASSEMBLY

00187VIP

FIG. 4 – 2 WAY MOTORIZED VALVE ASSEMBLY

00186VIP

DRAIN PIPING

Condensate drain lines must be installed with adequate

slope away from the unit to assure positive drainage.

YRHBC and YCHBC fan coil units require a minimum

trap of 1-1/2 inches be provided in the drain line to

assure proper drainage. YHBC, YPHBC, YHH, YPHH,

YHYB, and YPHYB fan coil units may be located where

the return air space is large enough that a negative

pressure is not present, however, a trapped condensate

line is recommended to ensure proper drainage of unit in

case a negative condition should occur (see Installation

Drawings for locations and sizes).

The drain should always be connected or piped to an

acceptable disposal point sloped away from the unit at

least 1/8" per foot

LD04801

FIG. 6 – TYPICAL CONDENSATE PIPING

UNIT

PRIMARY

SECONDARY

YHBC

3/4 MPT

5/8 OD

YPHBC

3/4 MPT

3/4 MPT

YRHBC

3/4 MPT

3/4 MPT

YHH

3/4 MPT

7/8 OD

YPHH

3/4 MPT

7/8 OD

YHYB

3/4 MPT

3/4 MPT

YPHYB

3/4 MPT

3/4 MPT

TABLE 2 - DRAIN LINE SIZES