Operation (special conditions) – Tripp Lite 3-Phase 20kVA User Manual

Page 9

Advertising
background image

9

Condition

LCD Display Message

Overload Shutdown

ON BYPASS
OVERLOAD 150%
SHUTDOWN...
VERSION: XXXXXXX

UPS Output Short Circuit

ON BYPASS
SHORT CIRCUIT!
SHUTDOWN...
VERSION: XXXXXXX

Overtemperature

ON BYPASS
HIGH TEMP!
SHUTDOWN...
VERSION: XXXXXXX

DC BUS Overvoltage

ON BYPASS
DC BUS O.V.P.!
SHUTDOWN...
VERSION: XXXXXXX

DC BUS Failure

ON BYPASS
DC BUS FAIL!
SHUTDOWN...
VERSION: XXXXXXX

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:

Condition

LCD Display Message

UPS Output Overload

OVERLOAD 110%

UPS Charger Failure

CHARGER FAILURE

Abnormal Input Frequency

FREQUENCY ERROR

Abnormal Input Phase

PHASE ABNORMAL!

Battery is Depleting*

ON BATTERY

Battery Charge is Nearly Depleted*

BATTERY LOW

* During a prolonged blackout, users should save files and shut down connected equipment.
The “BATTERY LOW” message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,”
“Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

R/S/T Inverter Output Failure

ON BYPASS
R OUTPUT FAIL!
SHUTDOWN...
VERSION: XXXXXXX

Low Battery

BYPS OFF NO O/P
LOW BATTERY!
SHUTDOWN...
VERSION: XXXXXXX

Remote Shutdown

BYPS OFF NO O/P
REMOTE SHUTDOWN
SHUTDOWN...
VERSION: XXXXXXX

Emergency Stop

BYPS OFF NO O/P
EMERGENCY STOP!
SHUTDOWN...
VERSION: XXXXXXX

Operation (Special Conditions)

(continued)

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive
filtered AC mains power, but will not receive battery power in the event of a blackout.

SWITCHING UPS TO “BYPASS” MODE

• Press the “OFF” button.

• Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.

• Turn the Main Input Switch Circuit Breaker OFF.

SWITCHING UPS TO “NORMAL” MODE

• Turn the Main Input Switch Circuit Breaker ON.

• Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.

• Press the “ON” button.