Technical specifications

14.1 General specifications

SIMATIC IPC427C

94

Operating Instructions, 04/2009, A5E02414743-01

General specifications
Ports
COM1; COM2 (optional)

RS232, max. 115 Kbps., 9-pin Cannon, male

VGA/DVI

VGA integrated in the DVI-I

Keyboard

USB support

Mouse

USB support

USB

4x USB 2.0 high-speed / high current

PROFIBUS / MPI interface, isolated
- Transmission speed

- Operating modes

9-pin Cannon socket, 2-row
9.6 Kbps to 12 Mbps

DP master: DP-V0, DP-V1 with SOFTNET-DP

DP slave: DP-V0, DP-V1 with SOFTNET DP slave

Ethernet

2x Ethernet ports (RJ45) Intel 82574L

10/100/1000 Mbps, isolated

Teaming-capable

CAN (on request)

Philips SJA1000

Status displays on the device
PWR

GREEN

Indicates correct supply voltage of 3.3 V, 5 V and 12 V from the

integrated power unit

OFF

Watchdog disabled

GREEN

Watchdog enabled, monitoring time not expire

WD

RED

Watchdog enabled, monitoring time expired

OFF

YELLOW

RED

Can be controlled by user programs

L1 (LED 1)
SF (Group fault)

RED

Can be controlled by controller program (e.g. WinAC)

OFF

YELLOW

GREEN

Can be controlled by user programs

L2 (LED 2)
RUN

STOP

GREEN

YELLOW

Can be controlled by controller program (e.g. WinAC)